Product Center






Product Details
Overview
Quick Details
- Place of Origin:
-
Jiangxi, China
- Brand Name:
-
JJXF
- Type:
-
Water Cannon
- Jet pressure(MPa):
-
0.8
- Flow rate::
-
40*(1±8%) L/s
- Shoot distance::
-
>=60 m
- Angle range::
-
+30~+70 degree
- Horizontal swing angle::
-
90 degree
- Max. Spray angle::
-
100 degree
- Weight:
-
21kgs
- Inlet:
-
65mm
Supply Ability
- Supply Ability
- 1000 Set/Sets per Quarter
Packaging & Delivery
- Packaging Details
- common packing/As clients 'request
- Port
- Jiujiang/shanghai/airport
- Lead Time:
-
Quantity(Sets) 1 - 100 >100 Est. Time(days) 2 To be negotiated
jiujiang fire equipement Water Cannon Firefighting Emergency Rescue Tools portable Fire Monitor
Product Description
Main Parts
1,water hose interface
2,manual up&down operation disk
3,the pressure gauge
4,manual left&right operation panel
5,manual spray quality operating disc
6,low voltage outlet
7,foam head
Test Items |
Standard |
Test results |
|
|
|
Qualified |
|
manoeuvrability |
Fire fighting monitor pitching rotation mechanism, horizontal swing mechanism, the control handle ( wheel ) should be flexible operation, safe and reliable transmission mechanism. Fire fighting gun pitching rotation mechanism with self-locking function or a locking device. Portable fire fighting monitor in the whole level rotation angle range minimum elevation angle injection should be stable and reliable, with no sliding and overturning phenomenon. |
Qualified |
|
decayresistance |
Fire fighting monitor should be adopt corrosion-resistant materials or the materials by the anti-corrosion treatment, so to meet the corresponding use of the environment and medium anti-corrosion. |
Qualified |
|
Specifications |
jet pressure (MPa) |
≤1.0 |
0.80 |
flow rate (L/s) |
40×(1±8%) |
39.8 |
|
visible distance (m) |
≥60 |
60.0 |
|
Minimum angle of elevation range (°) |
+30~+70 |
+30~+70 |
|
Level rotation angle (°) |
≥90 |
90 |
|
The maximum spray angle (°) |
≥90 |
100 |
|
Hydraulic sealing performance
|
Fire fighting monitor pressure element (except foam gun barrel ) according to the provisions of the water seal test 7.4, each connecting position should be no leakage phenomenon. |
Qualified |
|
Hydrostatic strength
|
Fire fighting monitor pressure element ( except the foam gun barrel) according to the provisions of the water pressure test for strength7.5, the gun body with no sweat, crack and permanent deformation and other defects. Seal test, each connecting position should be no leakage phenomenon. |
Qualified
|